Описание оборудования | |
---|---|
Current output 0/4 mA ... 20 mA | |
General specifications | |
Signal type | Analog input |
Functional safety related parameters | |
Safety Integrity Level (SIL) | SIL 2 |
Supply | |
Connection | terminals 9+, 10- or power feed module/Power Rail |
Rated voltage | 19 ... 30 V DC |
Ripple | within the supply tolerance |
Power dissipation/power consumption | ? 0.98 W / 0.98 W |
Interface | |
Programming interface | programming socket |
Input | |
Connection side | field side |
Connection | terminals 1, 2, 3, 4 |
RTD | type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995) type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94) type Cu10, Cu50, Cu100 (P50353-92) type Ni100 (DIN 43760) |
Thermocouples | type B, E, J, K, N, R, S, T (IEC584-1:1995) type L (DIN43710:1985) type TXK, TXKH, TXA (P8.585-2001) |
Potentiometer | 0 ... 20 k? (2-wire connection), 0.8 ... 20 k? (3-wire connection) |
Voltage | selectable within the range -100 ... 100 mV |
Input resistance | ? 1 M? (-100 ... 100 mV) |
Output | |
Connection side | control side |
Connection | terminal 5: source (-), terminal 6: source (+), terminal 7: sink(-), terminal 8: sink (+) |
Output | Analog current output |
Transfer characteristics | |
Deviation | |
Reaction time | worst case value (sensor breakage and/or sensor short circuit detection enabled) mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s |
Galvanic isolation | |
Input/Other circuits | basic insulation according to IEC 61010-1, rated insulation voltage 300 Veff |
Output/supply, programming input | functional insulation, rated insulation voltage 50 V AC There is no electrical isolation between the programming input and the supply. The programming cable provides galvanic isolation so that ground loops are avoided. |
Indicators/settings | |
Display elements | LEDs |
Configuration | via PACTware |
Labeling | space for labeling at the front |
Directive conformity | |
Electromagnetic compatibility | |
Conformity | |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529:2001 |
Ambient conditions | |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications | |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 100 g |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 |